[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932568":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932568,604,1,"单选题","某油浸变压器设置在高层商店建筑外的专用房间内，该变压器装油量为20t，下列说法中，正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","油浸变压器室与商店建筑的防火间距不应小于20m",false,{"key":16,"text":17,"correct":14},"B","油浸变压器室与商店建筑的防火间距不应小于30m",{"key":19,"text":20,"correct":14},"C","油浸变压器室专用房间的耐火等级不应低于一级",{"key":22,"text":23,"correct":24},"D","油浸变压器室专用房间的耐火等级不应低于二级",true,"根据《建筑设计防火规范》GB 50016—2014（2018年版）表3．4．1，变压器总油量为20t的室外变、配电站与高层民用建筑之间的防火间距不应小于25m，AB选项错误：根据5．4．12．燃油或燃气锅炉、油浸变压器、充有可燃油的高压电容器和多油开关等，宜设置在建筑外的专用房间内；确需贴邻民用建筑布置时，应采用防火墙与所贴邻的建筑分隔，且不应贴邻人员密集场所，该专用房间的耐火等级不应低于二级，C选项错误，D选项正确。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]