[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932547":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932547,604,1,"单选题","两座相邻的多层办公建筑，耐火等级均为三级，当相邻外墙均为未开设门、窗、洞口的不燃性墙体且无外露的可燃性屋檐，其防火间距不应小于（ ）m。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","3",false,{"key":16,"text":17,"correct":14},"B","3．5",{"key":19,"text":20,"correct":14},"C","5",{"key":22,"text":23,"correct":24},"D","6",true,"根据《建筑设计防火规范》GB 50016—2014（2018年版）表5．2．2注1，相邻两座单、多层建筑，当相邻外墙为不燃性墙体且无外露的可燃性屋檐，每面外墙上无防火保护的门、窗、洞口不正对开设且该门、窗、洞口的面积之和不大于外墙面积的5％时，其防火间距可按本表的规定减少25％。耐火等级为三级的多层民用建筑之间的的防火间距为8m，，当相邻外墙均为未开设门、窗、洞口的不燃性墙体且无外露的可燃性屋檐，是符合开设的洞口面积不大于外墙面积的5%要求。故可以减少25％，为6m。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]