[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932542":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932542,604,1,"单选题","某新建二级耐火等级的单层木器加工厂房，与相邻耐火等级为一级的高层综合楼裙房之间的防火间距不应小于（ ）m。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","25",false,{"key":16,"text":17,"correct":14},"B","50",{"key":19,"text":20,"correct":14},"C","13",{"key":22,"text":23,"correct":24},"D","10",true,"根据《建筑设计防火规范}GB 50016—2014（2018年版）表3．4．1，二级单层丙类木器厂房与一、二级裙房之间的防火间距不应低于10m。本题答案为D。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]