[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932539":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932539,604,2,"多选题","下列关于厂房、仓库耐火等级的说法，正确的是（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","粮食筒仓的耐火等级不应低于二级",true,{"key":16,"text":17,"correct":18},"B","使用或产生丙类液体的厂房，当其建筑面积不大于1000m2时，可采用三级耐火等级的建筑",false,{"key":20,"text":21,"correct":18},"C","高层厂房的耐火等级不应低于一级",{"key":23,"text":24,"correct":14},"D","储存可燃固体的多层丙类仓库，耐火等级不应低于三级",{"key":26,"text":27,"correct":14},"E","储存可燃液体的多层丙类仓库，其耐火等级不应低于二级","ADE","根据《建筑设计防火规范》GB50016—2014（2018版）3．2．8，粮食筒仓的耐火等级不应低于二级，二级耐火等级的粮食筒仓可采用钢板仓，A选项正确；根据3．2．3，使用或产生丙类液体的厂房和有火花、赤热表面、明火的丁类厂房，其耐火等级均不应低于二级，当为建筑面积不大于500m2的单层丙类厂房或建筑面积不大于1000m2的单层丁类厂房时，可采用三级耐火等级的建筑，B选项错误；根据3．2．2，高层厂房，甲、乙类厂房的耐火等级不应低于二级，C选项错误；根据3．2．7，高层仓库、储存可燃液体的多层丙类仓库，其耐火等级不应低于二级；储存可燃固体的多层丙类仓库和多层丁、戊类仓库，其耐火等级不应低于三级，DE选项正确。本题答案为ADE。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]