[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932532":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932532,604,1,"单选题","有火花、赤热表面、明火的丁类厂房，其耐火等级不应低于二级，当其建筑面积不大于（ ）m2，且层数为单层时，可采用三级耐火等级的建筑。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1000",true,{"key":16,"text":17,"correct":18},"B","1200",false,{"key":20,"text":21,"correct":18},"C","1500",{"key":23,"text":24,"correct":18},"D","2000","《建规》3.2.3，单、多层丙类厂房和多层丁、戊类厂房的耐火等级不应低于三级。使用或产生丙类液体的厂房和有火花、赤热表面、明火的丁类厂房，其耐火等级均不应低于二级，当为建筑面积不大于500m2的单层丙类厂房或建筑面积不大于1000m2的单层丁类厂房时，可采用三级耐火等级的建筑。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]