[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932306":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932306,604,1,"单选题","（2019年真题）某2层钢结构构成类洁净厂房，建筑高8m，长30m，宽20m，洁净区疏散走道靠外墙设置，关于该厂房防火设计的说法正确的是（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","该厂房可不设置消防给水设备",false,{"key":16,"text":17,"correct":18},"B","该厂房成产层，机房，站房均应设置火灾报警探测器",true,{"key":20,"text":21,"correct":14},"C","该厂房洁净区疏散走道自然排烟设施的有效排烟面积，不应小于走道建筑面积的20%",{"key":23,"text":24,"correct":14},"D","该厂房柱，粱的耐火极限可分别为2.00h，1.50h","P540-546 洁净厂房必须设置消防给水设施，故A选项错误 洁净厂房应设置火灾自动报警系统及消防联动控制，洁净厂房的生产层、技术夹层 、机房、站房等均应设置火灾报警探测器，生产区及走廊应设置手动火灾报警按钮。故B选项正确 洁净厂房的疏散走廊应采用机械排烟设施，故C选项说法不正确 洁净厂房的耐火等级不低于二级，柱的耐火极限不低于2.5h，梁的耐火极限不低于1.5h，故D选项说法错误",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]