[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932305":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932305,604,1,"单选题","（2016真题）洁净厂房内洁净室和疏散走道的顶棚的耐火极限分别不应低于（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.25h和1.0h",false,{"key":16,"text":17,"correct":18},"B","0.4h和1.0h",true,{"key":20,"text":21,"correct":14},"C","0.5h和0.5h",{"key":23,"text":24,"correct":14},"D","1.0h和0.5h","根据《洁净厂房设计规范》(GB50073)的规定，洁净室的顶棚、壁板及夹芯材料应为不燃烧体，且不得采用有机复合材料。顶棚和壁板的耐火极限不应低于0．4h，疏散走道顶棚的耐火极限不应低于1．0h。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]