[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932293":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932293,604,1,"单选题","（2018真题）根据现行国家标准《汽车库、修车库、停车场设计防火规范》关于汽车库排烟设计的说法，错误的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","建筑面积为 1000 ㎡的地下一层汽车库应设置排烟系统",false,{"key":16,"text":17,"correct":18},"B","自然排烟口的总面积不应小于室内地面面积的 1％",true,{"key":20,"text":21,"correct":14},"C","防烟分区的建筑面积不宜大于 2000m",{"key":23,"text":24,"correct":14},"D","用从顶棚下突出 0.5m 的梁来划分防烟分区","A正确，根据《汽车库、修车库、停车场设计防火规范》第8.2.1条,除敞开式汽车库、建筑面积小于1000m2的地下一层汽车库和修车库外,汽车库、修车库应设置排烟系统,并应划分防烟分区。 B错误，第8.2.4条,当采用自然排烟方式时,可采用手动排烟窗、自动排烟窗、孔洞等作为自然排烟口,并应符合下列规定:自然排烟口的总面积不应小于室内地面面积的2%。 C项、D项正确，第8.2.2条,防烟分区的建筑面积不宜大于2000m2且防烟分区不应跨越防火分区。防烟分区可采用挡烟垂壁、隔墙或从顶棚下突出不小于0.5m的梁划分。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]