[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932290":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932290,604,1,"单选题","（2017真题）根据《汽车库、修车库、停车场设计防火规范》GB 50967，关于室外消火栓用水量的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","II类汽车库、修车库、停车场室外消火栓用水量不应小于15L\u002Fs",false,{"key":16,"text":17,"correct":18},"B","I类汽车库、修车库、停车场室外消火栓用水量不应小于20L\u002Fs",true,{"key":20,"text":21,"correct":14},"C","III类汽车库修车库、停车场室外消火栓用水量不应小于10L\u002Fs",{"key":23,"text":24,"correct":14},"D","IV类汽车库修车库、停车场室外消火栓用水量不应小于5L\u002Fs","《汽车库规》7.1.5除本规范另有规定外，汽车库、修车库、停车场应设置室外消火栓系统，其室外消防用水量应按消防用水量最大的一座计算，并应符合下列规定： 1、I、Ⅱ类汽车库、修车库、停车场，不应小于20L\u002Fs 2、Ⅲ类汽车库、修车库、停车场。不应小于15L\u002Fs； 3、Ⅳ类汽车库、修车库、停车场，不应小于10L\u002Fs。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]