[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932278":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932278,604,1,"单选题","（2019年真题）某燃煤火力发电厂，单机容量200MW，该发电厂火灾自动报警系统的下列设计方案中，正确的是（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","运煤系统内的火灾探测器防护等级为IP65",true,{"key":16,"text":17,"correct":18},"B","厂区设置集中报警系统。",false,{"key":20,"text":21,"correct":18},"C","消防控制室与集中控制室分别独立设置",{"key":23,"text":24,"correct":18},"D","灭火过程中，消防水泵根据管网压力变化自动启停","P514-517 根据《火力发电厂与变电站设计防火标准》（GB50229-2019）中第7.13.2 条规定，单机容量为200MW及以上的燃煤电厂，应设置控制中心报警系统， 故B选项说法不正确 根据《火力发电厂与变电站设计防火标准》（GB50229-2019）中第7.13.4条规定， 消防控制室应与集中控制室合并设置，故C选项说法不正确 根据《火力发电厂与变电站设计防火标准》（GB50229-2019）中第7.13.13条规定，消防设施的就地启动、停止控制设备应具有明显标志，并应有防误操作保护措施。消防水泵的停运应为手动控制。消防水泵可按定期人工巡检方式设计。故D选项说法不正确",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]