[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932270":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932270,604,1,"单选题","（2016真题）某燃煤火力发电厂，单机容量为200MW，总容量为1000MW。下列关于该电厂消防设施的做法中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","消防控制室与主控制室合并设置",false,{"key":16,"text":17,"correct":18},"B","贮煤场的室外消防用水量采用15L\u002Fs",true,{"key":20,"text":21,"correct":14},"C","设置控制中心火灾自动报警系统",{"key":23,"text":24,"correct":14},"D","主厂房周围采用环状消防给水管网","《火力发电厂与变电设计站防火规范》(GB50229—2006)第7．12．4条规定，消防控制室应与单元控制室或主控制室合并设置，选项A正确。第7．2．2—3条规定，储煤场的消防用水量不应少于20L／s，选项B错误。第7．12．2条规定，单机容量为200MW及以上的燃煤电厂，应设置控制中心报警系统，选项C正确。第7．2．2～5条规定，主厂房、储煤厂(室内储煤场)、点火油罐区周围的消防给水管网应为环状，选项D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]