[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932255":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932255,604,1,"单选题","（2018真题）某城市交通隧道，封闭段长度为1500m，可通行危险化学品车，该隧道的下列防火设计方案中，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","隧道内的地下设备用房按二级耐火等级确定构件的燃烧性能和耐火极限",false,{"key":16,"text":17,"correct":14},"B","隧道的消防用房按二级负荷要求供电",{"key":19,"text":20,"correct":21},"C","采用耐火极限不低于2.00h的防火隔墙将隧道内设置的10Kv高压电缆与其它区域分隔",true,{"key":23,"text":24,"correct":14},"D","采用防火墙和甲级防火门将隧道内设置的可燃气体管道与其他区域分隔","隧道内的地下设备用房按一级耐火等级确定构件的燃烧性能和耐火极限 ，A错误。? 1500m，通行危险化学品车的为二类隧道，一、二类隧道的消防用电按一级负荷要求供电， B错误。 隧道内严禁设置可燃气体管道，电览槽应与其他管道分开，当设置10KV及以上的高压电缆时，应采用耐火极限不低于2.0小时的防火分隔体分隔。C正确，D错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]