[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932250":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932250,604,1,"单选题","（2019年真题）某地铁地上车站，建筑高度为18m，站台层与站厅层之间设有建筑面积为100㎡的商场，各层均能满足自然排烟条件。该车站的下列防火设计方案中，错误的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","车站站厅顶棚采用硅酸钙板，墙面采用烤瓷铝板、地面采用硬质PVC塑料地板进行装修，广告灯箱及座椅采用难燃聚氯乙烯塑料",false,{"key":16,"text":17,"correct":14},"B","沿车站的一个长边设置消防车道",{"key":19,"text":20,"correct":21},"C","车站站台至站厅的楼梯穿越商场的部位周围，设置耐火极限3.00h的防火墙分隔，且在商场疏散平台处开设的门洞采用甲级防火门分隔",true,{"key":23,"text":24,"correct":14},"D","车站的站厅公共区相邻两个安全出口之间的最小水平距离为20m","P473-474 在站厅非付费区的乘客疏散区外设置的商铺，不得经营和储存甲、乙类火灾危险性的商品，不得储存可燃性液体类商品。每个站厅商铺的总建筑面积不应大于100m2，单处商铺的建筑面积不应大于30m2。商铺应采用耐火极限不低于2.00h的防火隔墙或耐火极限不低于3.00h的防火卷帘与其他部位分隔，商铺内应设置火灾自动报警和灭火系统。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]