[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932243":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932243,604,1,"单选题","（2017真题）关于地铁防排烟设计的说法,正确的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","站台公共区每个防烟分区的建筑面积不宜超过2000m2",true,{"key":16,"text":17,"correct":18},"B","地下车站的设备用房和管理用房的防烟分区可以跨越防火分区",false,{"key":20,"text":21,"correct":18},"C","站厅公共区每个防烟分区的建筑面积不宜超过3000m2",{"key":23,"text":24,"correct":18},"D","地铁内设置的挡烟垂壁等设施的下垂高度不应小于450mm","地下车站的公共区，以及设备与管理用房，应划分防烟分区，且防烟分区不得跨越防火分区。B错误。 站厅与站台的公共区每个防烟分区的建筑面积不宜超过2000m2，设备与管理用房每个防烟分区建筑面积不宜超过750m2。A正确，C错误。 防烟分区可采取挡烟垂壁等措施。挡烟垂璧等设施的下垂高度不应小于500mm。D错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]