[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932241":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932241,604,1,"单选题","（2016真题）根据《地铁设计规范》GB50157-2013，下列关于地铁车站排烟风机耐高温性能的说法中，错误的是（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","地上设备与管理用房，排烟风机应保证在280℃是能连续有效工作0.5h",false,{"key":16,"text":17,"correct":14},"B","地下车站公共区，排烟风机应保证在250℃时能连续有效工作1h",{"key":19,"text":20,"correct":14},"C","区间隧道，排烟风机应保证在250℃时能连续有效工作1h",{"key":22,"text":23,"correct":24},"D","高架车站公共区，排烟风机应保证在280℃时能连续有效工作1h",true,"参《地铁设计规范》28.4.13：“区间隧道事故、排烟风机、地下车站公共区和站设备与管理用房排烟风机，应保证在250℃时能连续有效工作1”，28.4.14：“地面及高架车站公共区和设备与管理用房排烟风机应保证在280℃时能连续有效工作0.5h”。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]