[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932230":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932230,604,1,"单选题","（2016真题）对于石油化工企业，下列可燃气体，可燃烧体设备的安全阀出口连接方式中，不符合规范要求的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","泄放可能携带液滴的可燃气体应接至火炬系统",true,{"key":16,"text":17,"correct":18},"B","可燃液体设备的安全阀出口泄放管应接入储罐或其他容器",false,{"key":20,"text":21,"correct":18},"C","泄放后可能立即燃烧的可燃气体应经冷却后接至放空设施",{"key":23,"text":24,"correct":18},"D","可燃气体设备的安全阀出口泄放管应接至火炬系统或其他安全泄放设施","根据《石油化工企业设计防火规范》(GB50160)的规定，可燃气体、可燃液体设备的安全阀出口连接应符合下列规定：①可燃液体设备的安全阀出口泄放管应接入储罐或其他容器，泵的安全阀出口泄放管宜接至泵的人口管道、塔或其他容器；②可燃气体设备的安全阀出口泄放管应接至火炬系统或其他安全泄放设施；③泄放后可能立即燃烧的可燃气体或可燃液体应经冷却后接至放空设施；④泄放可能携带液滴的可燃气体应经分液罐后接至火炬系统。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]