[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932195":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932195,604,1,"单选题","（2018真题）关于建筑消防电梯设置的说法,错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","建筑高度为30m的物流公司办公楼可不设置消防电梯",false,{"key":16,"text":17,"correct":14},"B","埋深9m、总建筑面枳4000m2的地下室可不设置消防电梯",{"key":19,"text":20,"correct":21},"C","建筑高度为25m的门诊楼可不设置消防电梯",true,{"key":23,"text":24,"correct":14},"D","建筑高度为32m的住宅建筑可不设置消防电梯","建规-7.3.1下列建筑应设置消防电梯： 1.建筑高度大于33m的住宅建筑； 2.一类高层公共建筑和建筑高度大于32m的二类高层公共建筑；5层及以上且总建筑面积大于3000m2?(包括设置在其他建筑内五层及以上楼层）的老年人照料设施。 3.设置消防电梯的建筑的地下或半地下室，埋深大于10m且总建筑面积大于3000㎡的其他地下或半地下建筑(室)。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]