[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932192":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932192,604,1,"单选题","（2016真题）下列建筑中，允许不设置消防电梯的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","埋深为10m，总建筑而积为10000m2的地下商场",true,{"key":16,"text":17,"correct":18},"B","建筑高度为27m的病房楼",false,{"key":20,"text":21,"correct":18},"C","建筑高度为48m的办公建筑",{"key":23,"text":24,"correct":18},"D","建筑高度为45m的住宅建筑","根据《建筑设计防火规范》第 7.3.1 条，下列建筑应设置消防电梯：（1）建筑高度大于 33m 的住宅建筑；（2）一类高层公共建筑和建筑高度大于 32m 的二类高层公共建筑；（3）设置消防电梯的建筑的地下或半地下室，埋深大于 10m 且总建筑面积大于 3000㎡的其他地下或半地下建筑（室）。@##",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]