[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932146":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932146,604,1,"单选题","（2019年真题）某高层建筑内设置有常压燃气锅炉房，建筑体积为1000m3，燃气为天然气，建筑顶层未布置人员密集场所，该锅炉房的下列防火设计方案中，正确的是（）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","排风机正常通风量为5600m3\u002Fh",false,{"key":16,"text":17,"correct":14},"B","锅炉设置在屋顶上，距通向屋面的安全出口5m",{"key":19,"text":20,"correct":21},"C","在进入建筑物前和设备间内的燃气管道上设置自动和手动切断网",true,{"key":23,"text":24,"correct":14},"D","排风机事故通风量为10800m3\u002Fh","P158-162 燃油或燃气锅炉房、变压器室应设置在首层或地下一层的靠外墙部位，但常（负）压燃油或燃气锅炉可设置在地下二层或屋顶上。设置在屋顶上的常（负）压燃气锅炉，距离通向屋面的安全出口不应小于6m。故B选项说法错误 燃气锅炉房的正常通风量应按换气次数不少于6次\u002Fh确定，事故排风量应按换气次数不少于12次\u002Fh确定。 建筑体积为1000m3，排风机通风量为5600m3\u002Fh,即5.6次\u002Fh，故A选项错误 事故通风量为10800m3\u002Fh，即10.8次\u002Fh，故D选项错误",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]