[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932128":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932128,604,2,"多选题","（2017真题）某设计院对有爆炸危险的甲类厂房进行设计，下列防爆设计方案中，符合现行国家标准《建筑设计防火规范》GB50016 的有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","厂房承重结构采用钢筋混凝土结构",true,{"key":16,"text":17,"correct":14},"B","厂房的总控制室独立设置",{"key":19,"text":20,"correct":14},"C","厂房的地面采用不发火花地面",{"key":22,"text":23,"correct":14},"D","厂房的分控制室贴邻厂房外墙设置，并采用耐火极限不低于3.00h 的防火隔墙与其他部位分离",{"key":25,"text":26,"correct":27},"E","厂房利用门窗座位泄压设施，窗玻璃采用普通玻璃",false,"ABCD","《建规》3.6.1 有爆炸危险的甲、乙类厂房宜独立设置，并宜采用敞开或半敞开式。其承重结构宜采用钢筋混凝土或钢框架、排架结构。 3.6.8 有爆炸危险的甲、乙类厂房的总控制室应独立设置。 3.6.9 有爆炸危险的甲、乙类厂房的分控制室宜独立设置，当贴邻外墙设置时，应采用耐火极限不低于 3.00h 的防火隔墙与其他部位分隔。 3.6.6 散发较空气重的可燃气体、可燃蒸气的甲类厂房和有粉尘、纤维爆炸危险的乙类厂房，应符合下列规定： 1 应采用不发火花的地面。采用绝缘材料作整体面层时，应采取防静电措施；",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]