[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932113":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932113,604,2,"多选题","（2020年真题）某建筑高度为135m的办公楼,设置有避难层。关于该避层的说法，错误的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","第一个避难层的楼地面至灭火救援场地地面的高度不应大于50m",false,{"key":16,"text":17,"correct":18},"B","建筑至少应设置3个避难层",true,{"key":20,"text":21,"correct":14},"C","避难层应急疏散照明的地面最低水平照度不应低于3.0lx",{"key":23,"text":24,"correct":18},"D","避难层的设备间应采用耐火极限不低于1.50h的防火隔墙与避难区分隔",{"key":26,"text":27,"correct":18},"E","管道井直接开向避难区的门，与避难区出入口的距离不应小于4m","BDE","P167-169 第一个避难层（间）的楼地面至灭火救援场地地面的高度不应大于50m，A正确； 根据计算只需设置2个避难层就可以，B错误； 管道井和设备间应采用耐火极限不低于2.00h的防火隔墙与避难区分隔，管道井和设备间的门不应直接开向避难区；确需直接开向避难区时，与避难层区出入口的距离不应小于5m，且应采用甲级防火门。DE错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]