[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932098":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932098,604,1,"单选题","（2018真题）某建筑高度为36m的病房楼,共9层,每层建筑面枳3000m2,划分为3个护理单元。该病房避难间的下列设计方案中,正确的是（ ）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","将满足避难要求的监护室兼作避难间",true,{"key":16,"text":17,"correct":18},"B","在二至九层每层设置1个避难间",false,{"key":20,"text":21,"correct":18},"C","避难间的门采用乙级防火门",{"key":23,"text":24,"correct":18},"D","不靠外墙的避难间采用机械加压送风方式防烟","建规-5.5.24 高层病房楼应在二层及以上的病房楼层和洁净手术部设置避难间。避难间应符合下列规定: 1.避难间服务的护理单元不应超过2 个，其净面积应按每个护理单元不小于25.0m2?确定。 2.避难间兼作其他用途时，应保证人员的避难安全，且不得减少可供避难的净面积。 3.应靠近楼梯间，并应采用耐火极限不低于2.00h 的防火隔墙和甲级防火门与其他部位分隔。 4.应设置消防专线电话和消防应急广播。 5.避难间的入口处应设置明显的指示标志。 6.应设置直接对外的可开启窗口或独立的机械防烟设施，外窗应采用乙级防火窗。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]