[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932085":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932085,604,1,"单选题","（2015真题）某超高层办公建筑，建筑总高度为180m，共设置有3 个避难层。投入使用前对避难层进行检查，下列检查结果中，正确的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","设置了独立的机械排烟设施",false,{"key":16,"text":17,"correct":14},"B","第一个避难层的楼地面与灭火救援地地面的高差为55m",{"key":19,"text":20,"correct":21},"C","通向避难层的避难楼梯在避难层进行了分隔",true,{"key":23,"text":24,"correct":14},"D","避难层兼作设备层，避难区域与设备管道采用耐火极限1.0h 的防火墙分隔","避难层的设置，应保证第一个避难层（间）的楼地面至灭火枚援场地地面的高度不大于 50m, 两个避难层之间的高度不宜大于50m。避难层可兼作设备层，但设备管道宜集中布置，设备管道区应采用 耐火极限不低于 3. 00h 的防火隔墙与避难区分隔。通向避难层的防烟楼梯在避难层分隔、同层错位或上下层断开。避难层设置了消防电梯出口，消防专线电话和应急广播，消火栓和消防卷盘、防烟设施。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]