[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932084":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},932084,604,1,"单选题","（2017真题）关于疏散楼梯间设置的做法，错误的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","2层展览建筑无自然通风条件的封闭楼梯间，在楼梯间直接设置机械加压送风系统",false,{"key":16,"text":17,"correct":14},"B","与高层办公主体建筑之间设置防火墙的商业裙房，其疏散楼梯间采用封闭楼梯间",{"key":19,"text":20,"correct":14},"C","建筑高度为33m的住宅建筑，户门均采用乙级防火门，其疏散楼梯间采用敞开楼梯间",{"key":22,"text":23,"correct":24},"D","建筑高度为32m，标准层建筑面积为1500m2的电信楼，其疏散楼梯间采用封闭楼梯间",true,"建筑高度为 32m，标准层建筑面积为 1500 ㎡的电信楼属于一类高层公共建筑，应设置防烟楼梯间。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]