[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932078":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932078,604,1,"单选题","（2017真题）某7层商业综合体建筑，裙房与塔楼连通部位采用防火卷帘分隔。裙房地上3层，地下2层，建筑面积35000m2，耐火等级为一级，商业业务包括商业营业厅及餐厅等。裙房第三层的百人疏散宽度指标应为（）m\u002F百人。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.65",false,{"key":16,"text":17,"correct":18},"B","1.00",true,{"key":20,"text":21,"correct":14},"C","0.75",{"key":23,"text":24,"correct":14},"D","0.85","该商业综合体建筑为7层，故耐火等级应为一二级。裙房与塔楼连通部位采用防火卷帘分隔，故疏散并非完全独立设置，故疏散宽度指标为1.00m\u002F百人。@## 根据《建筑设计防火规范》第 5.5.21 条，每层的房间疏散门、安全出口、疏散走道和疏散楼梯的每 100 人最小疏散净宽度 (m\u002F百人）如下表所示：该商业综合体建筑为 7 层，故耐火等级应为一、二级。 裙房与主体的防火要求一致，所以裙房与塔楼连通部位采用防火卷帘分隔，故疏散并非完全独立设置，疏散宽度指标为1.00m\u002F百人。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]