[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932063":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932063,604,2,"多选题","（2016真题）下列关于防火分隔的做法中，正确的有（ ）",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","棉防织厂房在防火墙上设置一宽度为1.6m且耐火极限为2.0h的双扇防火门",true,{"key":16,"text":17,"correct":14},"B","5层宾馆共用一套通风空调系统，在竖向风管与每层水平风管交接处的水平管段上设置防火阀，平时处于常开状态",{"key":19,"text":20,"correct":21},"C","桶装甲醇仓库采用耐火极限为4.00h的防火墙划分防火分区，防火墙上设置1m宽的甲级防火门",false,{"key":23,"text":24,"correct":21},"D","分层商场内防火分区处的一个分隔部位的宽度为50m，该分隔部位使用防火卷帘进行分隔的最大宽度为20m",{"key":26,"text":27,"correct":14},"E","可停放300辆汽车的地下车库，每5个防烟分区共用一套的有排烟系统，排烟风管穿越防烟分区时设置排烟防火阀","ABE","根据《建筑设计防火规范》(GB50016)的规定，防火墙上不应开设门、窗、洞口，确需开设时，应设置不可开启或火灾时能自动关闭的甲级防火门、窗。甲级防火门的耐火极限不应低于1．5h。选项A正确。 通风和空气调节系统，横向宜按防火分区设置，竖向不宜超过5层。宾馆5层(竖向不宜超过5层)共用一套通风空调系统是可以的。防火阀平时处于开启状态，发生火灾时，当管道内烟气温度达到70％时，易熔合金片就会熔断断开，防火阀就会自动关闭。当建筑内每个防火分区的通风、空气调节系统均独立设置时，水平风管与竖向总管的交接处可不设置防火阀。除此之外，竖向风管与每层水平风管交接处的水平管段上都应设置防火阀。选项B正确。 仓库内的防火分区之间必须采用防火墙分隔，甲、乙类仓库内防火分区之间的防火墙不应开设门、窗、洞口。甲醇仓库的火灾危险性为甲类，选项C错误。 除中庭外，当防火分隔部位的宽度不大于30m时，防火卷帘的宽度不应大于10m；当防火分隔部位的宽度大于30m时，防火卷帘的宽度不应大于该部位宽度的1／3，且不应大于20m。商场的防火分隔部位宽度为50m，故防火卷帘的宽度为50×1÷3≈16．7(m)，即设置防火卷帘的宽度不应大于16．7m。选项D错误。 根据《汽车库、修车库、停车场设计防火规范》(GB50067)的规定，在穿过不同防烟分区的排烟支管上应设置烟气温度大于280℃时能自动关闭的排烟防火阀，排烟防火阀应联锁关闭相应的排烟风机。选项E正确。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]