[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932051":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},932051,604,2,"多选题","（2017真题）某商业建筑，建筑高度23.3m，地上标准层每层划分为面积相近的2个防火分区，防火分隔部位的宽度为60m，该商业建筑的下列防火分隔做法中，正确的有（）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","防火墙设置两个不可开启的乙级防火窗",false,{"key":16,"text":17,"correct":14},"B","防火墙上设置两樘常闭式乙级防火门",{"key":19,"text":20,"correct":21},"C","设置总宽度为18m，耐火极限为3.00h的特级防火卷帘",true,{"key":23,"text":24,"correct":21},"D","采用耐火极限为3.00h的不燃性墙体从楼地面基层隔断至梁或楼板底面基层",{"key":26,"text":27,"correct":14},"E","通风管道在穿越防火墙处设置一个排烟防火阀","CD","防火墙上不应开设门、窗、洞口，确需开设时，应设置不可开启或火灾时能自动关闭的甲级防火门、窗，因此AB错误；当防火分隔部位的宽度大于30m时，防火卷帘的宽度不应大于该部位宽度的1\u002F3，且不应大于20m，因此C正确；防火墙应直接设置在基础上火框架、梁等承重结构上，且为耐火极限不低于3.0h的不燃性墙体，因此D正确；排烟管进入排风机房处，穿越防火分区的排烟管道上，排烟系统的支管上。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]