[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932044":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},932044,604,1,"单选题","（2016真题）下列关于建筑的总平面布局中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","桶装乙醇仓库与相邻高层仓库的防火间距为15m",false,{"key":16,"text":17,"correct":14},"B","电解食盐水厂房与相邻多层厂区办公楼的防火间距为27m",{"key":19,"text":20,"correct":21},"C","发生炉煤气净化车间的总控制室与车间贴邻，并采用钢筋混凝土防爆墙分隔",true,{"key":23,"text":24,"correct":14},"D","空分厂房专用10KV变配电站采用设置甲级防火窗的防火墙与空分厂房一面贴邻","此题首先应判断选项中各类场所的火灾危险性类别。根据《建筑设计防火规范》(GB50016)的规定，乙醇仓库属于甲类仓库，甲类仓库与高层仓库的防火间距不应小于13m，选项A正确。电解食盐水厂房属于甲类厂房，甲类厂房与多层民用建筑防火间距不应小于25m，选项B正确。有爆炸危险的甲、乙类厂房的总控制室应独立设置，选项C错误。空分厂房是乙类厂房，变配电站不应设置在甲、乙类厂房内或贴邻，且不应设置在爆炸性气体、粉尘环境的危险区域内。供甲、乙类厂房专用的10kV及以下的变、配电站，当采用无门、窗、洞口的防火墙分隔时，可一面贴邻，并应符合《爆炸危险环境电力装置设计规范》(GB50058)等标准的规定。乙类厂房的配电站确需在防火墙上开窗时，应采用甲级防火窗，选项D正确。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]