[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932043":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},932043,604,1,"单选题","（2016真题）关于建筑防火分隔的做法中，错误的是( )。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","卡拉OK厅各厅室之间采用耐火极限为2.00h的防火墙面和1.5h的不燃性楼板和乙级防火门分隔",false,{"key":16,"text":17,"correct":18},"B","柴油发电机房内的储油问(柴油储量为0.8m3)，采用耐火极限为2.50h的防火隔墙和1.50h的不燃性楼板和甲级防火门与其他部位分隔",true,{"key":20,"text":21,"correct":14},"C","高层住宅建筑下部设置的商业服务网点，采用耐火极限为2.50h且无门、窗、洞口的防火隔墙和1.50h的不燃性楼板与其他部位分隔",{"key":23,"text":24,"correct":14},"D","医院病房内相邻护理单元之间采用耐火极限为2.00h的防火隔墙和乙级防火门分隔","《建筑设计防火规范》(GB50016—2014)规定，柴油发电机房内设置储油间时，其总储存量不应大于1m3，储油间应采用耐火极限不低于3.00h的防火隔墙与发电机间分隔;确需在防火隔墙上开门时，应设置甲级防火门。选项B中耐火极限为2.50h不符合规定。@##",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]