[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-932003":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},932003,604,1,"单选题","（2015真题）在标准耐火试验条件下，对一墙体进行耐火极限试验，试验记录显示，该墙体在受火作用至0.50h时粉刷层开始脱落，受火作用至1.00h时背火面的温度超过规定值，受火作用至1.20h时出现了穿透裂缝，受火作用至1.50h时墙体开始垮塌。该墙体的耐火极限是（ ）h。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1.0",true,{"key":16,"text":17,"correct":18},"B","0.5",false,{"key":20,"text":21,"correct":18},"C","1.2",{"key":23,"text":24,"correct":18},"D","1.5","耐火极限是指建筑构件按时间一温度标准曲线进行耐火试验，从受到火的作用时起，至失去承载能力、完整性或隔热性时止所用时间，用小时(h)表示。其中，承载能力是指在标准耐火试验条件下，承重或非承重建筑构件在一定时间内抵抗垮塌的能力；耐火完整性是指在标准耐火试验条件下，当建筑分隔构件某一面受火时，能在一定时间内防止火焰和热气穿透或在背火面出现火焰的能力；耐火隔热性是指在标准耐火试验条件下，当建筑分隔构件某一面受火时，能在一定时间内其背火面温度不超过规定值的能力。题中受火作用至1．00h时背火面的温度超过规定值，说明该墙体失去了耐火隔热性。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]