[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931986":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},931986,604,1,"单选题","（2015真题）某建筑高度为50m的宾馆，采用一路市政电源供电，柴油发电设备作为备用电源，建筑内的排烟风机采用主备电源自动切换装置。下列关于主备电源自动切换装置的设置中，不合理的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","自动切换装置设置在变电站内",true,{"key":16,"text":17,"correct":18},"B","自动切换装置设置在排烟风机房的风机控制配电箱内",false,{"key":20,"text":21,"correct":18},"C","主备电源自动切换时间为20s",{"key":23,"text":24,"correct":18},"D","主备电源自动切换时间为25s","当消防电源由自备应急发电机组提供备用电源时，消防用电负荷为一级或二级的要设置自动和手动启动装置，并在30s内供电。建筑高度为50m的宾馆属于一类高层建筑，按一级消防用电负荷供电。防排烟风机的两路低压电源应能在设备机房内自动切换。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]