[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931984":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},931984,604,1,"单选题","（2016真题）某高层宾馆，下列关于消防设备配电装置的做法中，不能满足消防设备供电要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","引至消防泵的两路电源在泵房内末端自动切换",false,{"key":16,"text":17,"correct":14},"B","消防负荷的配电线路设置短路动作保护装置",{"key":19,"text":20,"correct":21},"C","消防负荷的配电线路设置过负荷和过、欠电压保护装置",true,{"key":23,"text":24,"correct":14},"D","消防负荷的配电线路未设置剩余电流保护装置","消防水泵、防烟排烟风机及消防电梯的两路低压电源应能在设备机房内自动切换，选项A正确，其他消防设备的电源应能在每个防火分区配电间内自动切换，消防控制室的两路低压电源应能在消防控制室内自动切换。消防负荷的配电线路所设置的保护电器要具有短路保护功能，但不宜设置过负荷保护装置，如设置只能动作于报警而不能用于切断消防供电，选项B正确。消防负荷的配电线路不能设置剩余电流动作保护和过、欠电压保护，选项C错误、选项D正确。?",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]