[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931983":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931983,604,1,"单选题","（2017真题）下列消防配电设计方案中，符合规范要求的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","消防水泵电源由建筑一层低压分配电室出线",false,{"key":16,"text":17,"correct":14},"B","消防电梯配电线路采用树干式供电",{"key":19,"text":20,"correct":14},"C","消防配电线路设置过负载保护装置",{"key":22,"text":23,"correct":24},"D","排烟风机两路电源在排烟机房内自动切换",true,"A项消防水泵要由变配电站或主配电室直接出线，不符合要求；B项消防电梯要由变配电站或主配电室直接出线，采用放射式供电，不符合要求；C项消防配电线路所设置的保护电器要具有短路保护功能，但不宜设置过负载保护装置，不符合要求；D项防排烟风机的两路低压电源应能在设备机房内自动切换，即D是正确选项。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]