[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931982":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931982,604,2,"多选题","（2020年真题）某建筑高度为15m的3层公共建筑,每层建筑面积为1000m2，设有消火栓系统和自动喷水灭火系统。该建筑—层为超市,二层为电子游戏厅,三层为电影院。关于该建筑灭火器配置的说法,正确的有（ ）。",[11,15,18,21,24],{"key":12,"text":13,"correct":14},"A","超市的营业厅、电子游戏厅、电影院的观众厅应分别作为一个计算单元",true,{"key":16,"text":17,"correct":14},"B","计算单元的最小需配灭火级别的修正系数可取0.5",{"key":19,"text":20,"correct":14},"C","电子游戏厅单具灭火器最小配置灭火级别应为3A",{"key":22,"text":23,"correct":14},"D","电影院观众厅单具灭火器最小配置灭火级别应为2A",{"key":25,"text":26,"correct":27},"E","超市单具灭火器最小配置灭火级别应为3A",false,"ABCD","P557-562 同一计算单元不得跨越防火分区和楼层。A正确； 根据规范表格可知，修正系数是0.5，B正确； 1000m2的电子游戏厅都属于严重危险级，灭火级别为3A，C正确； 电影院的观众厅是中危险级（电影院的舞台及后台部分是严重危险级），灭火级别为2A，D选项正确； 超市为中危险级，灭火级别为2A，E选项错误。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]