[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931974":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931974,604,2,"多选题","（2019年真题）某地上商场，总建筑面积为4000㎡, 设置自动喷水灭火系统，采用直立型标准覆盖面积洒水喷头。 该喷头布置中，错误的有()",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","喷头呈正方形布置，边长为3. 8m",true,{"key":16,"text":17,"correct":14},"B","喷头呈平行四边形布置，长边和短边分别为3. 5m和1. 5m",{"key":19,"text":20,"correct":21},"C","喷头呈长方形布直，长边和短边分别为4. 0m和3.0m",false,{"key":23,"text":24,"correct":14},"D","喷头与端墙的距离为2. 0m",{"key":26,"text":27,"correct":21},"E","喷头与端墙的距离为0. 2m","ABD","P239-247 总建筑面积小于5000㎡的商场火灾危险性为中危险I级，本题目中场所为中危险I级场所。 根据《自动喷水灭火系统设计规范》（GB50084-2017）中7.1.2条规定，直立型、下垂型标准覆盖面积洒水喷头的布置，包括同一根配水支管上喷头的间距及相邻配水支管的间距，应根据设置场所的火灾危险等级、洒水喷头类型和工作压力确定，并不应大于表7.1.2的规定，且不应小于1.8m。 查表可知，中危险I级场所采用直立型标准覆盖喷头，正方形布置时边长不大于3.6m，矩形或平行四边形布置时长边长不大于4.0m,喷头与端墙最大距离1.8m，最小距离0.1m。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]