[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931947":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},931947,604,1,"单选题","（2016真题）下列建筑中的消防应急照明备用电源的连续供电时间按1.0h设置，其中不符 合规范要求的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","医疗建筑、老年人建筑",false,{"key":16,"text":17,"correct":14},"B","总建筑面积大于100000㎡的商业建筑",{"key":19,"text":20,"correct":21},"C","建筑高度大于于100m的住宅建筑",true,{"key":23,"text":24,"correct":14},"D","总建筑面积大于干20000㎡的地下汽车库","《建筑设计防火规范》(GB50016—2014)第10．1．5条规定，建筑内消防应急照明和灯光疏散指示标志的备用电源的连续供电时间应符合下列规定：①建筑高度大于100m的民用建筑，不应小于1．5h；②医疗建筑、老年人建筑、总建筑面积大于100000m2的公共建筑和总建筑面积大于20000m2的地下、半地下建筑，不应少于1．0h；③其他建筑，不应少于0．5h。选项C不符合要求。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]