[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931941":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931941,604,1,"单选题","（2020年真题）某建筑高度为99m的办公楼,地下2层,地上31层，防烟楼梯间和前室均设有机械加压送风系统,且地上部分与地下部分的加压送风系统分别独立设置。关于加压送风系统设置的说法,错误的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","该建筑地上部分的机械加压送风系统可不分段独立设置",false,{"key":16,"text":17,"correct":14},"B","前室应每层设一个常闭式加压送风口,并应设手动开启装置",{"key":19,"text":20,"correct":14},"C","采用机械加压送风的场所不宜设置可开启外窗",{"key":22,"text":23,"correct":24},"D","送风机的进风口与排烟口在同一面上时,两者的水平距离不应小于15m",true,"P488-495 送风机的进风口不应与排烟风机的出风口设在同一面上。当确有困难时，送风机的进风口与排烟风机的出风口应分开布置，且竖向布置时，送风机的进风口应设置在排烟出口的下方，其两者边缘最小垂直距离不应小于6.0m；水平布置时，两者边缘最小水平距离不应小于20.0m。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]