[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931937":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931937,604,1,"单选题","（2019年真题）当采用自然排烟方式时，储烟仓的厚度不应小于空间净高的（），且不应小于500mm，同时储烟仓底部距地面的高度应大于安全疏散所需的最小清晰高度。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","25%",false,{"key":16,"text":17,"correct":14},"B","15%",{"key":19,"text":20,"correct":14},"C","10%",{"key":22,"text":23,"correct":24},"D","20%",true,"P386-394 根据《建筑防烟排烟系统设计标准》（GB51251-2017）中第4.6.2条规定， 当采用自然排烟方式时，储烟仓的厚度不应小于空间净高的20%，且不应小于500mm；当采用机械排烟方式时，不应小于空间净高的10%，且不应小于500mm。同时储烟仓底部距地面的高度应大于安全疏散所需的最小清晰高度，最小清晰高度应按本标准的规定计算确定。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]