[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931922":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},931922,604,1,"单选题","（2018真题）某建筑高度为156m的公共建筑设有机械加压送风系统。根据现行囯家标准《建筑防烟排烟系统技术标准》（GB51251），该机械加压送风系统的下列设计方案中，错误的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","封闭避难层的送风是按避难层净面积每平方米不小于25m3\u002Fh确定",true,{"key":16,"text":17,"correct":18},"B","楼梯间与走道之间的压差为40Pa",false,{"key":20,"text":21,"correct":18},"C","前室与走道之间的压差为25Pa",{"key":23,"text":24,"correct":18},"D","机械加压送风系统按服务区段高度分段独立设置","封闭避难层（间）、避难走道的机械加压送风量应按避难层（间）、避难走道净面积每平方米不少于30m3\u002Fh计算。A错误。机械加压送风机的全压，除计算最不利管道压头损失外，还应有余压。机械加压送风量应满足走廊至前室至楼梯间的压力呈递增分布，余压值应符合下列要求: （1）前室、合用前室、消防电梯前室、封闭避难层（间）与走道之间的压差应为25-30Pa。 （2）防烟楼梯间、封闭楼梯间与走道之间的压差应为40-50 Pa。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]