[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931920":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},931920,604,1,"单选题","（2018真题）关于建筑机械防烟系统联动控制的说法，正确的是（ ）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","由同一防火分区内的两只独立火灾探测器作为相应机械加压送风机开启的联动触发信号",true,{"key":16,"text":17,"correct":18},"B","火灾确认后，火灾自动报警系统应能在30s内联动开启相应的机械加压送风机",false,{"key":20,"text":21,"correct":18},"C","加压送风口所在防火分区确认火灾后，火灾自动报警系统应仅联动开启所在楼层前室送风口",{"key":23,"text":24,"correct":18},"D","火灾确认后，火灾自动报警系统应能在20s内联动开启相应的常压加压送风口","防烟系统的联动控制设计。由加压送风口所在防火分区内的两只独立的火灾探测器或一只火灾探测器与一只手动火灾报警按钮的报警信号（\"与\"逻辑），作为送风口开启和加压送风机启动的联动触发信号，消防联动控制器在接收到满足逻辑关系的联动触发信号后，联动控制火灾层和相关层前室等需要加压送风场所的加压送风口开启和加压送风机启动。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]