[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931914":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931914,604,2,"多选题","（2020年真题）某办公楼设有闭式自动喷水灭火系统，地下一层为消防水泵房，消防水泵房内设置两台喷淋泵。关于喷淋泵控制的说法，正确的有（ ）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","喷淋泵应能手动启、停",true,{"key":16,"text":17,"correct":18},"B","喷淋泵应能自动启、停",false,{"key":20,"text":21,"correct":14},"C","喷淋泵控制柜在平时应设置在自动控制状态",{"key":23,"text":24,"correct":14},"D","喷淋泵控制柜应设置机械应急启泵功能",{"key":26,"text":27,"correct":14},"E","消防控制柜应设置专用线路连接的手动直接启泵按钮","ACDE","P475-480 消防水泵不应设置自动停泵的控制功能，B错误，停泵应由具有管理权限的工作人员根据火灾扑救情况确定。消防水泵控制柜在平时应使消防水泵处于自动启泵状态；防水泵应能手动启停和自动启动。消防控制柜或控制盘应设置专用线路连接的手动直接启泵按扭。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]