[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931904":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},931904,604,1,"单选题","（2019年真题）某三层办公建筑在底层设有低压配电间，每个楼层设有1个楼层配电箱，实测高压配电间的出线端固定准漏电流为800m A，每层准漏电流相同，该建筑设置电气火灾监控系统，未设置消防控制室，剩余电流式电气火灾监控探测器的下列设计方案中，错误的是（）",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","低压配电间的出线端设置1只探测器，探测器的报警电流设为1200mA",true,{"key":16,"text":17,"correct":18},"B","各楼层配电箱的进线端分别设置一只探测器，探测器的报警电流设为400mA",false,{"key":20,"text":21,"correct":18},"C","探测器采用独立式探测器",{"key":23,"text":24,"correct":18},"D","探测器报警时，不切断楼层配电箱的电源","P368-370 剩余电流式电气火灾监控探测器应以设置在低压配电系统首端为基本原则，宜设置在第一级配电柜（箱）的出线端。在供电线路泄露电流大于 500mA 时，宜在其下一级配电柜（箱）设置。 选择剩余电流式电气火灾监控探测器时，应计及供电系统自然漏流的影响，并应选择参数合适的探测器；探测器报警值宜为 300mA～500mA 。故A选项中说法错误",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]