[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931903":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},931903,604,1,"单选题","（2019年真题）某化工厂主控楼设置了消防控制室，生产装置拟设置可燃气体探测报警系统。该火灾可燃气体探测报警系统的下列设计方案中，错误的是（）",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","可燃气体探测器设置在可燃气体管道阀门、进料口等部位附近",false,{"key":16,"text":17,"correct":14},"B","可燃气体探测器同时接入生产装置的DCS系统和可燃气体报警控制器",{"key":19,"text":20,"correct":21},"C","可燃气体探测器直接将报警信号传输至消防控制室图形显示装置",true,{"key":23,"text":24,"correct":14},"D","可燃气体报警控制器设置在防护区附近","P365-368 可燃气体探测器将泄漏可燃气体的浓度参数转变为电信号，传输到可燃气体报警控制器。或直接由可燃气体探测器做出泄漏可燃气体浓度超限报警判断，将报警信息传输到可燃气体报警控制器。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]