[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931900":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931900,604,1,"单选题","（2019年真题）某商场设置火灾自动报警系统，首层2个防火分区共用火灾报警控制器的2#回路总线。其中防火分区-设置30只感烟火灾探测器、10只手动火灾报警按钮、10只总线模块（②输入2输出）；防火分区二设置28只感烟火灾探测器、8只手动火灾报警按钮、10只总线模块（2输入2输出）。控制器2#回路总线设置短路隔离器的数量至少为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","3只",false,{"key":16,"text":17,"correct":14},"B","6只",{"key":19,"text":20,"correct":14},"C","5只",{"key":22,"text":23,"correct":24},"D","4只",true,"P347-365 每只总线短路隔离器保护的火灾探测器、手动火灾报警按钮和模块等消防设备的总数不应超过32点；总线穿越防火分区时，应在穿越处设置总线短路隔离器。防火分区1共有50点，设置2只短路隔离器；防火分区2共有46点，设置2只短路隔离器。故一共需设4只短路隔离器",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]