[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931899":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931899,604,2,"多选题","（2019年真题）某办公楼的自动喷水灭火系统采用湿式系统。通过（）可直接自动启动该湿式系统的消防水泵。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","手动火灾报警按钮",false,{"key":16,"text":17,"correct":14},"B","每个楼层设置的水流指示器",{"key":19,"text":20,"correct":21},"C","消防水泵出水干管上设置的压力开关",true,{"key":23,"text":24,"correct":21},"D","高位消防水箱出水管上的流量开关",{"key":26,"text":27,"correct":21},"E","报警阀组压力开关","CDE","P347-365 根据《自动喷水灭火系统设计规范》（GB50084-2017）中第11.0.1规定，湿式系统、干式系统应由消防水泵出水干管上设置的压力开关、高位消防水箱出水管上的流量开关和报警阀组压力开关直接自动启动消防水泵。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]