[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931890":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931890,604,2,"多选题","（2018真题）根据现行国家标准《火灾自动报警系统设计规范》（GB 50116），消防联动控制器应具有切断火灾区域及相关区域非消防电源的功能。当局部区域发生电气设备火灾时，不可立即切断的非消防电源有（）。",[11,15,19,22,25],{"key":12,"text":13,"correct":14},"A","客用电梯电源",true,{"key":16,"text":17,"correct":18},"B","空调电源",false,{"key":20,"text":21,"correct":14},"C","生活给水泵电源",{"key":23,"text":24,"correct":18},"D","自动扶梯电源",{"key":26,"text":27,"correct":14},"E","正常照明电源","ACE","根据《火灾自动报警系统设计规范》(GB50116-2013)第4.10.1条文说明,(1)火灾时可立即切断的非消防电源有:普通动力负荷、自动扶梯、排污泵、空调用电康乐设施、厨房设施等。(2)火灾时不应立即切断的非消防电源有:正常照明、生活给水泵、安全防范系统设施、地下室排水系、客梯和Ⅰ一Ⅲ类汽车库作为车辆疏散口的提升机。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]