[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931887":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931887,604,1,"单选题","（2018真题）根据现行国家标准《火灾自动报警系统设计规范》GB50116，关于电气火灾监控探测器设置的说法，正确的是（ ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","剩余电流式电气火灾监控探测器应以设置在低压配电系统的末端配电柜内",false,{"key":16,"text":17,"correct":14},"B","在无消防控制室且电气火灾监控探测器设置数量不超过10只时，非独立式电气火灾监控探测器可接入火灾报警控制器的探测器回路",{"key":19,"text":20,"correct":14},"C","电气火灾监控探测器发出报警信号后，应在3s内联动电气火灾监控器切断保护对象的供电电源",{"key":22,"text":23,"correct":24},"D","设有消防控制室时，电气火灾监控器的报警信息应在集中火灾报警控制器上显示",true,"剩余电流式电气火灾监控探测器的设置剩余电流式电气火灾监控探测器应以设置在低压配电系统首端为基本原则，宜设置在第一级配电柜（箱）的出线端。A错误。 电气火灾监控探测器不可接入火灾报警控制器的探测器回路，BC错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]