[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931886":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},931886,604,1,"单选题","（2018真题）根据现行国家标准《火灾自动报警系统设计规范》（GB50116），关于火灾探测器设置的说法正确的是（ ）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","在2.8m宽的走道顶棚上安装的点型感温火灾探测器之间的间距不应超过15m",false,{"key":16,"text":17,"correct":14},"B","相邻两组线型光束感烟火灾探测器的水平距离不应超过15m",{"key":19,"text":20,"correct":14},"C","管路采样吸气式感烟火灾探测器的一个探测单元的采样管总长不宜超过100m",{"key":22,"text":23,"correct":24},"D","点型感烟火灾探测器距墙壁的水平距离不应小于0.5m",true,"在宽度小于3m的内走道顶棚上设置点型探测器时，宜居中布置。感温火灾探测器的安装间距不应超过10m;感烟火灾探测器的安装间距不应超过15m;探测器至端墙的距离，不应大于探测器安装间距的1\u002F2。A错误。相邻两组线型光束感烟火灾探测器的水平距离不应超过14m，B错误。 管路采样吸气式感烟火灾探测器的一个探测单元的采样管总长不宜超过200m，C错误。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]