[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931882":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},931882,604,1,"单选题","（2016真题）下列关于建筑防烟系统联动控制要求的做法中，错误的是（ ）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","常闭加压送风口开启由其所在防火分区内两只独立火灾探测器的报警信号作为联动触发信号",false,{"key":16,"text":17,"correct":14},"B","加压送风机启动由其所在防火分区内的一只火灾探测器与一只手动火灾报警按钮的报警信号作为联动触发信号",{"key":19,"text":20,"correct":21},"C","楼梯间的前室或合用前室的加压送风系统中任一常闭加压送风口开启时，联动启动该楼梯间各楼层的前室及合用前室内的常闭加压送风口",true,{"key":23,"text":24,"correct":14},"D","对于防火分区跨越多个楼层的建筑，楼梯间的前室或合用前室内任一常闭加压送风口开启时联动启动该防火分区内全部楼层的楼梯间前室及合用前室内的常闭加压送风口","防烟系统的联动控制设计：由加压送风口所在防火分区内的两只独立的火灾探测器（选项A正确）或一只火灾探测器与一只手动报警按钮的报警信号（选项B正确），作为送风口开启和加压送风机启动的联动触发信号，消防联动控制器在接收到满足逻辑关系的联动触发信号后，联动控制火灾层和相关层前室等需要加压送风场所的加压送风口开启（选项C错误，选项D正确）和加压送风机启动。",{"id":6,"name":27,"category":28,"favorite":29},"消防安全技术实务(一级)","建筑工程",0]