[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-931824":3},{"question":4,"library":30},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":28,"analysis":29},931824,604,2,"多选题","（2018真题）某固定顶储罐，储存5000m3航空煤油。该储罐低倍数泡沫灭火系统可选用（ ）。",[11,15,18,22,25],{"key":12,"text":13,"correct":14},"A","半固定式液下喷射系统",true,{"key":16,"text":17,"correct":14},"B","半固定式液上喷射系统",{"key":19,"text":20,"correct":21},"C","固定式半液下喷射系统",false,{"key":23,"text":24,"correct":21},"D","固定式液上喷射系统",{"key":26,"text":27,"correct":21},"E","固定式液下喷射系统","AB","航空煤油也即三号喷气燃料,是非水溶性,其闪点为38℃。根据《泡沫灭火系统设计规范》（GB50151-—2010）第4.1.2条,储罐区低倍数泡沫灭火系的选择,应符合下列规定:非水溶性甲、乙、丙类液体国定顶储罐,应选用液上喷射、液下喷射或半液下喷射系统。提醒:此处不适用第5.2.1条,丙类国定顶与内浮顶油罐,单罐容量小于10000m3的甲乙类固定顶与内浮顶油罐,当选用中倍数泡沫灭火系统时,宜为固定式。根据《石油化工企业设计防火规范》（GB50160-2008）第8.7.2条,下列场所应采用固定式泡沫灭火系统: （1）甲、乙类和闪点等于或小于90℃的丙类可燃液体的固定顶罐及浮盘为易熔材料的内浮顶罐: ①单罐容积等于或大于10000m的非水溶性可燃液体储罐; ②单罐容积等于或大于50m3的水溶性可燃液体储罐; （2）甲、乙类和闪点等于或小于90℃的丙类可燃液体的浮顶罐及浮盘为非易熔材料的内浮顶罐:单罐容积等于或大于5000m3的非水溶性可燃液体储罐; （3）移动消防设施不能进行有效保护的可燃液体储罐。第8.7.3条,下列场所可采用移动式泡沫灭火系统: （1）罐壁高度小于7m或容积等于或小于200m3的非水溶性可燃液体储罐;（2）润滑油储罐;（3）可燃液体地面流淌火灾、油池火灾。第8.7.4条,除本规范第8.7.2条及第8.7.3条规定外的可燃液体罐宜采用半固定式泡沫灭火系统。",{"id":6,"name":31,"category":32,"favorite":33},"消防安全技术实务(一级)","建筑工程",0]